Viton "O"-Rings Failure
Recently, an operator took a controlled shutdown at a major deep-water production
platform following six observed gas leaks to atmosphere in similar circumstances, all from
valves in the HP and IP service (600 psi or greater). The valve failures included 10- and
12-inch valves five with trace leakage and one with significant (8 mcf) leakage.
Following an investigation, the operator reports the failure mechanism to be explosive
decompression (ED) of High Flourine and Flourocarbon (commonly referred to as "Viton
family") elastomer o-ring seals. Explosive decompression is a process in which gases
that have been trapped within the given material are rapidly expanded, causing seals to
blister, crack, and fail. The Viton elastomer is commonly found in ball valves, check
valves, rotating equipment seals, and pressure safety valves.
Of concern to the operator are the following elastomers: (1) High Flourine FKM (such as
Viton GF) elastomers, used in "o"-ring seals and which are apparently not
explosive-decompression resistant at certain operating pressures; (2) Flourocarbon FKM
(such as Viton A & B) elastomer, unless quality controlled with regard to hardness and
other properties.
The operator inspected more than 100 components following the above failures. Over 70
percent of the Viton elements inspected are possibly defective or questionable, suffering
some degree of explosive decompression. High Flourine FKM was more susceptible to ED than
other elastomers.
The operator concluded that some FKM elastomers are not resistant to explosive
decompression at certain operating pressures. In addition, some laboratory analysis to
date demonstrates that some elastomers exhibit hardness (a key quality regarding ED
resistance) below the product specification range. The operator concluded that some
Flourocarbon FKM used in more recently commissioned projects are less ED resistant than
samples taken from earlier construction.
The operator has recommended that inventories of the subject elastomers be checked to
ensure that they are of the required quality and specification for an operation. These
include materials that may have been obtained over the last 36 months. The operator also
recommends that inventories be checked to ensure that elastomers are not being
inappropriately used in pressures for which they do not meet the design criteria. The
elastomer materials in question may have been used in valves constructed by several
manufacturers within the last 36 months.
The MMS has not carried out independent tests to confirm the above data for the purpose
of this Safety Alert. However, the MMS believes the data presented are of importance to
the industry and recommends operators review their individual use of the above materials.
|